vde-2025-096

CRITICAL CVSS 9.8 csaf_weidmuellerinterfacegmbhcokg
Description

An unauthenticated remote attacker can exploit several vulnerabilities in Weidmueller devices Energy Meter 750-24 and Energy Meter 750-230 to ultimately gain full system access and remote code execution.

Timeline
Published
2026-03-10 07:00 UTC
Last Modified
2026-03-10
CVSS Details

CVSS details not available.

Affected Products

No product information available.

Weaknesses (CWE)
References

No references available.

Linked Vulnerabilities

No linked vulnerabilities found.

{
  "document": {
    "acknowledgments": [
      {
        "organization": "CERT@VDE",
        "summary": "coordination",
        "urls": [
          "https://certvde.com"
        ]
      }
    ],
    "aggregate_severity": {
      "namespace": "https://www.first.org/cvss/v3.1/specification-document",
      "text": "High"
    },
    "category": "csaf_security_advisory",
    "csaf_version": "2.0",
    "distribution": {
      "tlp": {
        "label": "WHITE",
        "url": "https://www.first.org/tlp/"
      }
    },
    "lang": "en-GB",
    "notes": [
      {
        "category": "summary",
        "text": "An unauthenticated remote attacker can exploit several vulnerabilities in Weidmueller devices Energy Meter 750-24 and Energy Meter 750-230 to ultimately gain full system access and remote code execution.",
        "title": "Summary"
      },
      {
        "category": "general",
        "text": "As a general security measure, Weidmueller strongly recommends to change the default passwords and to minimize the network exposure of products. Limit access to trusted networks by using the appropriate mechanisms.",
        "title": "General Recommendation"
      },
      {
        "category": "description",
        "text": "These vulnerabilities in combination allow an unauthenticated remote attacker to fully compromise the system including remote code execution. Further details on each separate vulnerability can be found under vulnerability details.",
        "title": "Impact"
      },
      {
        "category": "description",
        "text": "It is strongly advised to update to the newest version. The vulnerabilities are fixed in version 3.14.",
        "title": "Remediation"
      }
    ],
    "publisher": {
      "category": "vendor",
      "contact_details": "psirt@weidmueller.com",
      "name": "Weidmueller Interface GmbH & Co. KG",
      "namespace": "https://www.weidmueller.com"
    },
    "references": [
      {
        "category": "external",
        "summary": "Weidmueller Security Advisory Board",
        "url": "https://support.weidmueller.com/support-center/popular-resources/security-advisory-board"
      },
      {
        "category": "external",
        "summary": "CERT@VDE Security Advisories for Weidmueller",
        "url": "https://certvde.com/de/advisories/vendor/weidmueller/"
      },
      {
        "category": "self",
        "summary": "VDE-2025-096: Weidmueller: Multiple vulnerabilities in Energy Meter 750-24 and Energy Meter 750-230 - HTML",
        "url": "https://certvde.com/de/advisories/VDE-2025-096"
      },
      {
        "category": "self",
        "summary": "VDE-2025-096: Weidmueller: Multiple vulnerabilities in Energy Meter 750-24 and Energy Meter 750-230 - CSAF",
        "url": "https://weidmueller.csaf-tp.certvde.com/.well-known/csaf/white/2026/vde-2025-096.json"
      }
    ],
    "title": "Weidmueller: Multiple vulnerabilities in Energy Meter 750-24 and Energy Meter 750-230",
    "tracking": {
      "aliases": [
        "VDE-2025-096",
        "WMSA-2600001"
      ],
      "current_release_date": "2026-03-10T07:00:00.000Z",
      "generator": {
        "date": "2026-03-09T12:47:31.897Z",
        "engine": {
          "name": "Secvisogram",
          "version": "2.5.44"
        }
      },
      "id": "VDE-2025-096",
      "initial_release_date": "2026-03-10T07:00:00.000Z",
      "revision_history": [
        {
          "date": "2026-03-10T07:00:00.000Z",
          "number": "1.0.0",
          "summary": "Initial version"
        }
      ],
      "status": "final",
      "version": "1.0.0"
    }
  },
  "product_tree": {
    "branches": [
      {
        "branches": [
          {
            "branches": [
              {
                "category": "product_name",
                "name": "ENERGY METER 750-24",
                "product": {
                  "name": "ENERGY METER 750-24",
                  "product_id": "CSAFPID-11001",
                  "product_identification_helper": {
                    "model_numbers": [
                      "2540900000"
                    ]
                  }
                }
              },
              {
                "category": "product_name",
                "name": "ENERGY METER 750-230",
                "product": {
                  "name": "ENERGY METER 750-230",
                  "product_id": "CSAFPID-11002",
                  "product_identification_helper": {
                    "model_numbers": [
                      "2540910000"
                    ]
                  }
                }
              }
            ],
            "category": "product_family",
            "name": "Hardware"
          },
          {
            "branches": [
              {
                "category": "product_version",
                "name": "3.13",
                "product": {
                  "name": "Firmware 3.13",
                  "product_id": "CSAFPID-21001",
                  "product_identification_helper": {
                    "cpe": "cpe:2.3:o:weidmueller:energy_meter_750_firmware:3.13:*:*:*:*:*:*:*"
                  }
                }
              },
              {
                "category": "product_version",
                "name": "3.14",
                "product": {
                  "name": "Firmware 3.14",
                  "product_id": "CSAFPID-21002",
                  "product_identification_helper": {
                    "cpe": "cpe:2.3:o:weidmueller:energy_meter_750_firmware:3.14:*:*:*:*:*:*:*"
                  }
                }
              },
              {
                "category": "product_version_range",
                "name": "vers:generic/<=3.13",
                "product": {
                  "name": "Firmware <=3.13",
                  "product_id": "CSAFPID-21003"
                }
              }
            ],
            "category": "product_family",
            "name": "Firmware"
          }
        ],
        "category": "vendor",
        "name": "Weidmueller"
      }
    ],
    "product_groups": [
      {
        "group_id": "CSAFGID-0001",
        "product_ids": [
          "CSAFPID-31001",
          "CSAFPID-31002",
          "CSAFPID-31003",
          "CSAFPID-31004"
        ],
        "summary": "Affected products."
      },
      {
        "group_id": "CSAFGID-0002",
        "product_ids": [
          "CSAFPID-32001",
          "CSAFPID-32002"
        ],
        "summary": "Fixed products."
      }
    ],
    "relationships": [
      {
        "category": "installed_on",
        "full_product_name": {
          "name": "Firmware 3.13 installed on ENERGY METER 750-24",
          "product_id": "CSAFPID-31001",
          "product_identification_helper": {
            "cpe": "cpe:2.3:o:weidmueller:energy_meter_750_24_firmware:3.13:*:*:*:*:*:*:*"
          }
        },
        "product_reference": "CSAFPID-21001",
        "relates_to_product_reference": "CSAFPID-11001"
      },
      {
        "category": "installed_on",
        "full_product_name": {
          "name": "Firmware 3.13 installed on ENERGY METER 750-230",
          "product_id": "CSAFPID-31002",
          "product_identification_helper": {
            "cpe": "cpe:2.3:o:weidmueller:energy_meter_750_230_firmware:3.13:*:*:*:*:*:*:*"
          }
        },
        "product_reference": "CSAFPID-21001",
        "relates_to_product_reference": "CSAFPID-11002"
      },
      {
        "category": "installed_on",
        "full_product_name": {
          "name": "Firmware 3.14 installed on ENERGY METER 750-24",
          "product_id": "CSAFPID-32001",
          "product_identification_helper": {
            "cpe": "cpe:2.3:o:weidmueller:energy_meter_750_24_firmware:3.14:*:*:*:*:*:*:*"
          }
        },
        "product_reference": "CSAFPID-21002",
        "relates_to_product_reference": "CSAFPID-11001"
      },
      {
        "category": "installed_on",
        "full_product_name": {
          "name": "Firmware 3.14 installed on ENERGY METER 750-230",
          "product_id": "CSAFPID-32002",
          "product_identification_helper": {
            "cpe": "cpe:2.3:o:weidmueller:energy_meter_750_230_firmware:3.14:*:*:*:*:*:*:*"
          }
        },
        "product_reference": "CSAFPID-21002",
        "relates_to_product_reference": "CSAFPID-11002"
      },
      {
        "category": "installed_on",
        "full_product_name": {
          "name": "Firmware <=3.13 installed on ENERGY METER 750-24",
          "product_id": "CSAFPID-31003"
        },
        "product_reference": "CSAFPID-21003",
        "relates_to_product_reference": "CSAFPID-11001"
      },
      {
        "category": "installed_on",
        "full_product_name": {
          "name": "Firmware <=3.13 installed on ENERGY METER 750-230",
          "product_id": "CSAFPID-31004"
        },
        "product_reference": "CSAFPID-21003",
        "relates_to_product_reference": "CSAFPID-11002"
      }
    ]
  },
  "vulnerabilities": [
    {
      "cve": "CVE-2025-41709",
      "cwe": {
        "id": "CWE-78",
        "name": "Improper Neutralization of Special Elements used in an OS Command ('OS Command Injection')"
      },
      "notes": [
        {
          "category": "description",
          "text": "An unauthenticated remote attacker can perform a command injection via Modbus-TCP or Modbus-RTU to gain read and write access on the affected device.",
          "title": "CVE Description"
        }
      ],
      "product_status": {
        "fixed": [
          "CSAFPID-32001",
          "CSAFPID-32002"
        ],
        "known_affected": [
          "CSAFPID-31001",
          "CSAFPID-31002",
          "CSAFPID-31003",
          "CSAFPID-31004"
        ]
      },
      "remediations": [
        {
          "category": "vendor_fix",
          "details": "Update to version 3.14",
          "product_ids": [
            "CSAFPID-31001",
            "CSAFPID-31002",
            "CSAFPID-31003",
            "CSAFPID-31004"
          ]
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "attackComplexity": "LOW",
            "attackVector": "NETWORK",
            "availabilityImpact": "HIGH",
            "baseScore": 9.8,
            "baseSeverity": "CRITICAL",
            "confidentialityImpact": "HIGH",
            "environmentalScore": 9.8,
            "environmentalSeverity": "CRITICAL",
            "integrityImpact": "HIGH",
            "privilegesRequired": "NONE",
            "scope": "UNCHANGED",
            "temporalScore": 9.8,
            "temporalSeverity": "CRITICAL",
            "userInteraction": "NONE",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H",
            "version": "3.1"
          },
          "products": [
            "CSAFPID-31001",
            "CSAFPID-31002",
            "CSAFPID-31003",
            "CSAFPID-31004"
          ]
        }
      ],
      "title": "Command injection in power analyzer via Modbus-TCP and Modbus-RTU"
    },
    {
      "cve": "CVE-2025-41710",
      "cwe": {
        "id": "CWE-798",
        "name": "Use of Hard-coded Credentials"
      },
      "notes": [
        {
          "category": "description",
          "text": "An unauthenticated remote attacker may use hardcodes credentials to get access to the previously activated FTP Server with limited read and write privileges.",
          "title": "CVE Description"
        }
      ],
      "product_status": {
        "fixed": [
          "CSAFPID-32001",
          "CSAFPID-32002"
        ],
        "known_affected": [
          "CSAFPID-31001",
          "CSAFPID-31002",
          "CSAFPID-31003",
          "CSAFPID-31004"
        ]
      },
      "remediations": [
        {
          "category": "vendor_fix",
          "details": "Update to version 3.14",
          "product_ids": [
            "CSAFPID-31001",
            "CSAFPID-31002",
            "CSAFPID-31003",
            "CSAFPID-31004"
          ]
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "attackComplexity": "LOW",
            "attackVector": "NETWORK",
            "availabilityImpact": "NONE",
            "baseScore": 6.5,
            "baseSeverity": "MEDIUM",
            "confidentialityImpact": "LOW",
            "environmentalScore": 6.5,
            "environmentalSeverity": "MEDIUM",
            "integrityImpact": "LOW",
            "privilegesRequired": "NONE",
            "scope": "UNCHANGED",
            "temporalScore": 6.5,
            "temporalSeverity": "MEDIUM",
            "userInteraction": "NONE",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:L/A:N",
            "version": "3.1"
          },
          "products": [
            "CSAFPID-31001",
            "CSAFPID-31002",
            "CSAFPID-31003",
            "CSAFPID-31004"
          ]
        }
      ],
      "title": "Use of Hard-coded Credentials in power analyzer"
    },
    {
      "cve": "CVE-2025-41711",
      "cwe": {
        "id": "CWE-327",
        "name": "Use of a Broken or Risky Cryptographic Algorithm"
      },
      "notes": [
        {
          "category": "description",
          "text": "An unauthenticated remote attacker can use firmware images to extract password hashes and brute force plaintext passwords of accounts with limited access. ",
          "title": "CVE Description"
        }
      ],
      "product_status": {
        "fixed": [
          "CSAFPID-32001",
          "CSAFPID-32002"
        ],
        "known_affected": [
          "CSAFPID-31001",
          "CSAFPID-31002",
          "CSAFPID-31003",
          "CSAFPID-31004"
        ]
      },
      "remediations": [
        {
          "category": "vendor_fix",
          "details": "Update to version 3.14",
          "product_ids": [
            "CSAFPID-31001",
            "CSAFPID-31002",
            "CSAFPID-31003",
            "CSAFPID-31004"
          ]
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "attackComplexity": "LOW",
            "attackVector": "NETWORK",
            "availabilityImpact": "NONE",
            "baseScore": 5.3,
            "baseSeverity": "MEDIUM",
            "confidentialityImpact": "LOW",
            "environmentalScore": 5.3,
            "environmentalSeverity": "MEDIUM",
            "integrityImpact": "NONE",
            "privilegesRequired": "NONE",
            "scope": "UNCHANGED",
            "temporalScore": 5.3,
            "temporalSeverity": "MEDIUM",
            "userInteraction": "NONE",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:N",
            "version": "3.1"
          },
          "products": [
            "CSAFPID-31001",
            "CSAFPID-31002",
            "CSAFPID-31003",
            "CSAFPID-31004"
          ]
        }
      ],
      "title": "Use of a Broken or Risky Cryptographic Algorithm for firmware images of power analyzer"
    },
    {
      "cve": "CVE-2025-41712",
      "cwe": {
        "id": "CWE-732",
        "name": "Incorrect Permission Assignment for Critical Resource"
      },
      "notes": [
        {
          "category": "description",
          "text": "An unauthenticated remote attacker who tricks a user to upload a manipulated HTML file can get access to sensitive information on the device. This is a result of incorrect permission assignment for the web server.",
          "title": "CVE Description"
        }
      ],
      "product_status": {
        "fixed": [
          "CSAFPID-32001",
          "CSAFPID-32002"
        ],
        "known_affected": [
          "CSAFPID-31001",
          "CSAFPID-31002",
          "CSAFPID-31003",
          "CSAFPID-31004"
        ]
      },
      "remediations": [
        {
          "category": "vendor_fix",
          "details": "Update to version 3.14",
          "product_ids": [
            "CSAFPID-31001",
            "CSAFPID-31002",
            "CSAFPID-31003",
            "CSAFPID-31004"
          ]
        }
      ],
      "scores": [
        {
          "cvss_v3": {
            "attackComplexity": "LOW",
            "attackVector": "NETWORK",
            "availabilityImpact": "NONE",
            "baseScore": 6.5,
            "baseSeverity": "MEDIUM",
            "confidentialityImpact": "HIGH",
            "environmentalScore": 6.5,
            "environmentalSeverity": "MEDIUM",
            "integrityImpact": "NONE",
            "privilegesRequired": "NONE",
            "scope": "UNCHANGED",
            "temporalScore": 6.5,
            "temporalSeverity": "MEDIUM",
            "userInteraction": "REQUIRED",
            "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:N/A:N",
            "version": "3.1"
          },
          "products": [
            "CSAFPID-31001",
            "CSAFPID-31002",
            "CSAFPID-31003",
            "CSAFPID-31004"
          ]
        }
      ],
      "title": "Incorrect Permission Assignment on power analyzer"
    }
  ]
}
View JSON API Download JSON